Slow the Flow

Sustainable drainage · Field testing

Infiltration test calculator

Turn timed water-level readings into a measured infiltration rate for each trial pit fill. Compare repeats and record the rate you adopt for your design.

Give feedback

Before you start

Have your site investigation log, pit references and dimensions, soil and groundwater observations, and timed water levels for each fill to hand. This calculator covers open, empty, rectangular trial pits with vertical sides. Filled, irregular or borehole tests need a method suited to their geometry.

Normally complete at least three separate fill-and-drain tests at each pit location. Three readings from one fill count as one test. Use “Add repeat fill” for each refill. A complete test must cover the fall from 75% to 25% of its initial water depth. Record the actual starting water depth immediately after filling. If the water never reaches the lower threshold, keep the readings as an incomplete test.

Project record

Pit details

Use the same ground datum for pit depth and dip readings. Changing convention reinterprets the entries for every fill in this pit.

How the water level is measured

Timed readings and drawdown

Paste two columns from a field sheet or type one reading per line: elapsed minutes, then water level in metres. Start at zero minutes. For example, 10, 0.75 records a level of 0.75 m after ten minutes.

Calculated infiltration rate · selected fill

Compare pits and repeat fills

Adopted design rate

Identify the pit and fills relevant to the proposed feature. Explain any excluded tests, variation between fills, ground conditions and any allowance applied. The designer selects the rate.

Use the same pit and report references in the First 5 mm checklist, water quality assessment and planning application checklist. Where a field asks for mm/h, use the converted value shown in the exported report.

Calculation method and limits

For each fill, H is the initial water depth above the base. The calculator interpolates between consecutive observed readings to find the times at 75% and 25% of H. For internal length L and width W, the volume lost is L × W × H / 2. The wetted area at half depth, including the base, is L × W + (L + W) × H. Divide volume by wetted area and elapsed seconds to obtain m/s. Multiply by 3,600,000 for mm/h.

Interpret the test alongside the ground investigation, groundwater levels, pollution risk and proposed infiltration level. Record incomplete fills and consider whether the test depth and location represent the design. The calculator does not establish infiltration suitability or size a soakaway.

BRE Digest 365, Soakaway design (2016) · National SuDS standards for England

Report

Free tool for the SuDS community. Slow the Flow accepts no design responsibility for projects using this tool. The designer remains responsible for the inputs, interpretation and suitability of the design.

Draft stored in this browser.